Standard Transformer Housings
Explosion Relief
Where the customer believes there might be a remote chance of an explosion
and/or fire as a result of failure in the equipment protected by the enclosure,
then a number of options are available to contain the failure.
Envico's solution to this problem is a special design which allows the
roof of the enclosure to lift when such an explosion takes place, releasing
the force of the explosion safely upwards. The roof then returns to its
normal position.
Envico enclosures have been comprehensively tested under the severest
conditions by several leading British laboratories and have been found
to satisfy all criteria. See
link to video example.
Fire Retardancy and Fire Retardancy Materials
Four levels of fire retardantcy materials are available depending on the
customers application. They are defined in 'Resin systems to BS 476: Part
7'.
The degree of fire retardancy in the material supplied by Envico is measured
by the surface spread of flames test (British Standard 476 part 7).
These are:
General Purpose. Where no particular fire rating is required; a lower
cost material is available.
Class 2. Flame spread no greater than 215 mm in the first 1 ½ minutes
and an overall spread of no more than 455 mm in ten minutes.
Class 1. Flame spread no greater than 165 mm in ten minutes.
Class 0. Normal Building Regulation rating and not a British Standard
Classification. It must meet Class 1 for spread of flames and also meet
the fire propagation requirements of BS 476 Part 6.
Specialist Mouldings
Design
Envico design all their buildings in accordance with BS 6399, Part 2:
Code of Practice for wind loadings; and, Part 3: Code of practice for
imposed roof loads, resulting in a construction that will provide excellent
strength and longevity of service in all conditions for many years.
We also provide a full CAD service to design your building to your exacting
requirements, and if required we can superimpose your equipment drawings
to visualize the layout and highlight any potential conflicts before the
build.
Construction
All our buildings incorporate industry leading materials. We use only
hardwood WBP (Weather and Boil Proof) ply for the walls, and combined
with every building individually engineered for its location, provides
a very robust construction.
Insulation
Our standard construction provides a U-value of 2.2 W/m2/°C, whilst
being able to provide higher U values of 1.8 through to 0.4. We can also
achieve higher values of 0.35 and 0.25 for walls and roof respectively,
and even meet the 25% improvement in insulation on these values to meet
new government targets for CO2 emission (2010 Target Emissions Rate).
Sound Attenuation
When you need to reduce the sound energy emitted by your equipment, Envico
can offer a range of nominal attenuation levels. Our standard construction
offers a nominal 24dba acoustic performance, other standard level of attenuation
are: 26, 30-32, 35, 40 and 45 dBA.
HVAC
Envico will calculate the ventilation system most suited to your application.
This is based on the equipment heat that requires dissipation, the desired
internal operating temperature of the housing against the external ambient.
Whether this be natural ventilation, forced ventilation, Air Conditioning
or Air Handling system.
Electrical
As part of the Morgan GRP group Envico has access to NICEIC approved contractors,
all the electrical installations are carried out in accordance with current
IEE regulations BS7671:2008 and to 17th Edition Regulations. Zone 0, 1
or 2 installation’s can also be offered. Installation of customer’s
equipment can also be carried out at Envico.
Steel Options
Deflection calculations are performed on every steel base in accordance
with client equipment specification. A full design service is provided
to ensure the customer’s equipment interfaces correctly with the
base, cable and pipe apertures and corresponding gland plates can also
be incorporated.
Steel platforms and staircases are designed in accordance with the following
British Standards:
BS5395: Part 1, Code of Practice for the design, construction and maintenance
of straight stairs and winders
BS5395: Part 3, Code of Practice for the design of industrial type stairs,
permanent ladders and walkways
External Finishes
 |
Semi-Gloss: The Envico semi-gloss finish exhibits
a smart, modern appearance. Our extensive manufacturing facilities
mean we can provide building sizes to your exact requirements, in
a time frame to suit the demands of your schedule. |
 |
Textured: Envico’s budget finish provides
excellent value for money with a traditional stippled appearance.
Despite being a value solution, high quality materials are used in
its construction to ensure longevity of service. |
 |
Brick Effect: An excellent alternative finish when
the surroundings of your new enclosure require a traditional look.
With a range of different brick and pointing colours, a brick effect
enclosure looks extremely effective and takes a fraction of the time
to build compared with a normal brick build. |
 |
Stone: The Envico stone finish is hand crafted
to blend into your specific site requirements; this can even include
replicating moss! Envicos stone finish enclosures have been used by
the Environment Agency where the impact on the local surroundings
has to be minimal. |
 |
Wood Grain: Our simulated wood grain reproduced
a very effective timber effect. Wood grain wall panels and doors are
available in a variety of colours, or combining a timber effect door
with the stone or brick finish gives a very realistic traditional
finish. |
The colour of your enclosure can be chosen from the BS5252 or RAL colour
charts. Follow the link below to view an online colour chart.
http://www.llewellyn-ryland.co.uk/bs5252range.html
http://www.llewellyn-ryland.co.uk/ralrange.html
Standard colours we hold in stock are:
14 C 39 British Racing Green
10 A 07 Hurricane Grey
10 A 05 Goosewing Grey
00 A 05 Dove Grey
08 B 21 Kashmir Beige
00 E 55 White
08 B 29 Peat
Warranty
Our warranty period is 12 months. In order to safeguard
our reputation the company has a policy of replacing faulty components
at any time after the warranty period has expired, at its sole
discretion and dependent on circumstances.
Download our Terms
& Conditions of Sale
|